This recall has been updated. Changes have been made to the product description and recall advertisement. Cabling and electrical devices sold as part of 'SmartSpace' kit homes prior to July 2015. Cable SDI CABLE 1.5mm² V90 450/750V TO AS/NZS 5000.2 YAFEI SRF CABLE 3 x 2.5mm² 450/750V V90 TO AS/NZS 5000.2 YAFEI SRF CABLE 3 x 1.5mm² 450/750V V90 TO AS/NZS 5000.2 YAFEI Circuit Breaker and Residual Current Device (RCD) Marked JVM21-63 C16 240/415V~ Marked RCBO JVL5 C16 30mA 240V~
Why it was recalled
The cables have failed some of the required ageing tests of AS/NZS 5000.2. The insulation could become prematurely brittle with age. If the insulation becomes brittle and the cables are disturbed, the insulation could break and expose live conductors, resulting in possible electric shock or fires. The circuit breaker and RCD do not pose a safety risk, however these components are not approved for sale in Australia.
Hazard
Electrical shock and fire.